Even though I completely answered this question a few years ago (not), I need to revisit the requirements for thermal insulation.
We're in zone 4 Marine, according to the 2018 Seattle Energy Code, Chapter 3.
- The 2018 Seattle Energy Code for zone Marine 4 dictates:
- Windows U-Factor 0.30
- Skylight U-Factor 0.50
- Ceiling R-Value R-49 (R402.2.1 says R-38 is enuf?)
- Wall R-Value R-21 intermediate framing - this is why 2x6 studs
- Floor R-Value R-30
- Slab: R-10, 2 feet depth
The International Energy Conservation Code is strict. Luckily, it doesn't apply.
Ceiling: R-49 (R-60 per Intl Energy Conservation Code)
Wall: R-13 (R-20 or 13+5ci per IECC)
Slab: R-10, 2 feet depth (10ci, 4 feet depth per IECC)
ci = Continuous Insulation
13+ci or 13+5 means R-13 cavity insulation plus R-5 continuous insulation or insulated siding
Table N1102.1.3 in the 2021 IRC
City of Seattle Department of Construction & Inspections (SDCI)
Energy Code 2018 Seattle Energy Code (Energy code advisor Duane Jonlin duane.jonlin@seattle.gov)
- 3 General Requirements
- Looks like King County is designated Zone 4 Marine.
- 4 Residential Energy Efficiency
- 5 Existing Buildings
- Table R402.1.1
- R502.1: "Additions to an existing building...shall conform [to rules for new]...without requiring the unaltered portion of the...building...to comply."
Includes Building Envelope as well as Lighting
Residential Code SRC, which adopts the 2018 Intl Residential Code with amendments
- 3 Building Planning
- R302.11 Fireblocking in walls
- 4 Foundations
- 5 Floors
- Table R502.3.1 gives floor joist spans 30 or 4psf live, 10 or 20 dead
- Table R502.3.3 is allowable cantilever for joists supporting ext bearing wall and roof
- R502.7 - blocking and bridging
- R503 is floor sheathing
- 6 Wall Construction
- R602.3 framing diagram - balloon framing still ok
- Table R602.7 for headers - depends on snow load (30-50-70 psf) and building width (12'-24'-36')
- 602.10.2 "Braced wall panels" - they mean shear
- 7 Wall Covering
- 5/8 Type X for "garage clg beneath habitable rooms"--I think we're good in the main part of the garage. 6" oc fasteners.
- Vapor retarder is required (on the int side, behind the drywall) because we're in Zone 4 Marine
- Seattle has replaced the 15# felt paragraph with a "Water-resistive barrier" paragraph which allows 15# felt
- 8 Roof-Ceiling
- Table R802.4 has rafter spans
- Table R802.5 has ceiling joist spans
- 9 Roof Assemblies
- Allowed underlayment is in terms of ASTM standards. Under asphalt shingles, D226 Type I, D4869 Types I-IV, or D6757 are allowed
- 10 Chimneys and Fireplaces (also 18 Chimneys and Vents)
- 11 Energy Efficiency - Nope, fooled you. Seattle has not adopted Ch. 11. They have the Seattle Energy Conservation Code instead.
- 20 Water Heaters